Structural Engineering notes for GATE, PSUs - part 1

Hello, How you doing?



 I just picked following information for the structural Engineers, I hope this is useful:


  • Minimum 4 Nos. of bars for rectangular columns and 6 Nos. for circular columns are to be used.
  • Lapping is not allowed for the bars having diameter more than 36 mm.
  •  For chairs minimum 12 mm diameter bars are to be used.
  • For dowel minimum of 12 diameter bars should be used.
  • Main bars in slab shall not be less than 8 mm (HYSD) diameter and 10 mm (Plain bars) diameters.
  • Longitudinal reinforcement should not be less than 0.8% and not more than 6% of the gross C/S.
  • Minimum thickness of slab is 125 mm.
  •  A maximum of 1.5 m of free fall is allowed for concrete pouring.
  • pH value of water used shall not be less than 6.
  • In steel reinforcement 8 kg of winding wire is required per MT.